ANTSPACE HD5
$128,000.00| Specifications | 1Set 1500KW 308 Rack Space |
| Shipping Weight, T | 12 |
| Operating Weight, T | 13.5 |
| Heat Dissipation Capacity | 1500kW |
| Outlet water temperature @30˚C ambient temperature | 35℃±1˚C |
| Container Certification | CCS |
| Safety Certification | NFPA 79:2021 UL 508A:2018 R8.21 CSA C22.2 No. 14-18 IEC 60204 Ed 5.1 2009 |
| Input Voltage and Frequency | 400V±5% 50/60Hz |
| Operationg Power, kW | ≤80 |
| Connection interface (Container) | DN100(ISO2852 PN16) |
| Connection Interface (Drain Pipe) | DN20(Tapered tube) |
| Noise @25℃, 15m | 75dBA |
| Coolant Usage, m³ | 2.1 |
ANTSPACE HW5
$84,000.00| Specifications | 1Set 1200KW 210 Rack Space |
| Shipping weight, T | 14 |
| Operating weight, T | 24 |
| Main switch of power distribution cabinets, A | 1200*2 |
| Rated current, A | ≤986 |
| Rated Current per Miner, A | ≤10 |
| Inlet cable | The inlet cables can withstand high-voltage of above 600V, with the following requirements: L1 single core cable 600kcMil(300mm²)x4 L2 single core cable 600kcMil(300mm²)x4 L3 single core cable 600kcMil(300mm²)x4 N Single-core cable 600kcMil(300mm²)x4 PE single-core cable 500kcMil(240mm²)x2 |
| Flow rate, m³/h | ≥85 |
| Quantity of ANTSPACE powered by one 2500kVA Transformer | 2 |
| Dry-Wet Tower | |
| Heat Dissipation Capacity, kW | 1200 kW |
| Outlet Temperature @ 28℃ Wet Bulb Temperature | 35℃ |
| Container Certification | China Classification Society Certification |
| Operating Power, kW | 15~29 |
| Motor Rated Voltage and Frequency | 400V±5% 50/60Hz |
| Motor Rated Voltage and Frequency | DN40(Internal thread) |
| Drain Pipe Interface | DN65(Internal thread) |
| Noise Level @25℃, 15m | 70 dBA |
| Water Consumption, m³/h | 0.7~1.3m³/h |